Chamber Selection – Type C Cavity Drain Systems

Not suitable for Surface water calculations or foul water calculations

Chamber selection - Groundwater

Please add values

Basement m2 floor and walls

m2

Basement floor above or below water table

Depth of incoming pipe from underside of slab

mm

Static Head to (inlet of pump to high point of pipe)

m
Chamber height required 0 mm
Incoming flow rate 0 l/s
Pumps/Total head (l/s) 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0
V3 2.2 1.8 1.3 0.7 0.0 0.0 0.0 0.0 0.0 0.0
V4 0.0 3.0 2.8 2.4 1.9 1.5 1.0 0.0 0.0 0.0
V6 0.0 3.7 3.3 3.0 2.7 2.4 2.1 1.4 1.2 0.4
Please note:
  • Any highlighted fields can be used but only the min chamber specification will be shown.
  • Pumps selection is based on optimum/ideal performance based on pump performance curve.
  • Pumps suggested are in Delta range (V3, V4 and V6).

Based on

  • Static Head set at 3m depth
  • Discharge is 50mm on all (2")
  • Less than a 10m horizontal run - anything over please call
  • 0.1l/s per 100 m² of basement floor and wall area for basements above the water table
  • 0.2l/s per 100 m² of floor and wall area for basements below the water table
  • Allow a safety factor of 5 when selecting a pump duty
  • If no amounts are highlighted please call us

Chat with a member of our team

Get in touch
Delta
Cookie Settings

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.